一、有关层流手术室的建筑布局、基本装备、净化空调系统和用房分级等应符合《医院洁净手术部建筑技术规范GB50333-2002》的标准。
1、 The building layout, basic equipment, purification air conditioning system and room classification of laminar flow operating room should comply with the standard of "technical code for building clean operating Department of hospital (GB 50333-2002)".
二、进入到手术室清洁区后、洁净区域内的人员应更换专用的洁净服。
2、 After entering the operating room cleaning area, the personnel in the clean area should change the special clean clothes.
三、洁净手术部各区域的缓冲区,需要设有明显的标识和屏障,各自区域的门应该时刻保持关闭的状态,并有连锁装置,不可同时打开出、入门。
3、 Clear signs and barriers should be set in the buffer zone of each area of clean operating department. The doors of each area should be kept closed at all times, and there should be interlock device. It is not allowed to open the entrance and exit at the same time.
五、洁净手术部的净化空调系统应当在手术前30分钟开启;洁净手术部的净化空调系统应当连续运行,直至清洁、消毒工作完成。Ⅰ~Ⅱ级用房的运转时间为清洁、消毒工作完成后20分钟,Ⅲ~Ⅳ级用房的运转时间为清洁、消毒工作完成后30分钟。
5、 The clean air conditioning system of the clean operating department shall be started 30 minutes before the operation; the air conditioning system of the clean operating department shall be in continuous operation until the cleaning and disinfection work is completed. The operation time of class I ~ II rooms is 20 minutes after the completion of cleaning and disinfection work, and the operation time of class III ~ IV rooms is 30 minutes after the completion of cleaning and disinfection.
六、对洁净区域内的非阻漏式孔板、格栅、丝网等送风口,应当每周进行清洁,若有污染应随时清洁
6、 The air supply outlets such as non leak proof orifice plate, grille and wire mesh in the clean area shall be cleaned weekly. If there is any pollution, it shall be cleaned at any time
七、对洁净区域内回风口格栅应当使用竖向栅条,每天擦拭清洁1次,每周彻底清洁,若有污染应随时清洁,对滤料层应按表3要求更换。
7、 The air return grille in the clean area shall be cleaned with vertical bars once a day and cleaned thoroughly every week. If there is any pollution, it shall be cleaned at any time. The filter material layer shall be replaced according to the requirements in Table 3.
八、负压手术室每次手术结束后应当进行负压持续运转15分钟后再进行清洁擦拭,达到自净要求方可进行下一个手术。过滤致病气溶胶的排风过滤器应当每半年更换一次
8、 After each operation, the negative pressure operating room should be operated continuously for 15 minutes before cleaning and wiping. The next operation can be carried out after reaching the self-cleaning requirements. The exhaust filter for filtering pathogenic aerosol should be replaced every six months
九、对凝结水的排水点应当每天检查,并每周进行清洁。

9、 The drain point of condensate should be checked every day and cleaned weekly.

昆山昌瑞空调净化技术有限公司,专注从事空气过滤器系列产品(初/中/高效、化学过滤器等)、洁净室净化设备(抛弃式/可更换式/自动卷绕式过滤器、高效送风口、FFU高效过滤器净化机组)的研发、生产、销售和售后。

Changrui Air Conditioning Purification Technology Co., Ltd. focuses on the R&D, production, sales and after-sales of air filter series products (primary/medium/high-efficiency, chemical filters, etc.) and clean room purification equipment (disposable/replaceable/automatic winding filters, high-efficiency air supply outlets, FFU high-efficiency filter purification units).